EN 12464-1 lux level table: Em, UGR, Uo and Ra by room

The values below follow EN 12464-1:2021 for 90 common indoor task areas — maintained illuminance Em, glare limit UGR, uniformity Uo and colour rendering Ra. Use it for a first sizing pass and a specification cross-check, then confirm against your national adoption (DIN EN, NF EN, NEN-EN, UNI EN, UNE-EN, BS EN) and the project brief. This table is a design aid, not a replacement for the standard.

Free to reuse in tender documents and design reports with a credit link to led-project-light.com.

90 of 90 rows

EN 12464-1:2021 maintained illuminance, UGR, uniformity and colour rendering by indoor task area
Building typeTask or activity areaEm (lx)UGR maxUo minRa minReferenceDesign notes
OfficeFiling, copying, circulation inside the office300190.4806.2 Table 6.2
OfficeWriting, typing, reading, data processing500190.6806.2 Table 6.2Add 750 lx for open-plan desks used by older occupants
OfficeTechnical drawing by hand750160.7806.2 Table 6.2
OfficeCAD workstations500190.6806.2 Table 6.2Limit screen-reflected luminance to 200-1500 cd/m2
OfficeConference and meeting rooms500190.6806.2 Table 6.2Dimmable to 200 lx for projection
OfficeReception desk300220.6806.2 Table 6.2
OfficeArchives200250.4806.2 Table 6.2
OfficeCoworking / flexible desking500190.6806.2 Table 6.2Zone controls per desk cluster
EducationClassroom, general teaching300190.6806.3 Table 6.3
EducationClassroom for evening classes and adult education500190.6806.3 Table 6.3
EducationLecture hall500190.6806.3 Table 6.3Dimmable, separate front-of-room circuit
EducationBlackboard / whiteboard500190.7806.3 Table 6.3Asymmetric wallwasher, avoid specular reflection
EducationDemonstration table500190.7806.3 Table 6.3
EducationArt rooms500190.6806.3 Table 6.3
EducationArt rooms in art schools750190.7906.3 Table 6.3Ra 90+ and 5000 K for colour judgement
EducationTechnical drawing rooms750160.7806.3 Table 6.3
EducationPractical rooms and laboratories500190.6806.3 Table 6.3
EducationHandicraft and teaching workshops500190.6806.3 Table 6.3
EducationMusic practice rooms300190.6806.3 Table 6.3
EducationComputer practice rooms300190.6806.3 Table 6.3
EducationPreparation rooms and workshops500220.6806.3 Table 6.3
EducationEntrance halls200220.4806.3 Table 6.3
EducationCirculation areas and corridors100250.4806.3 Table 6.3
EducationStairs150250.4806.3 Table 6.3Vertical illuminance on treads is the design driver
EducationStudent common rooms and assembly halls200220.4806.3 Table 6.3
EducationTeachers rooms300190.6806.3 Table 6.3
EducationLibrary: bookshelves200190.6806.3 Table 6.3Vertical illuminance on shelf face
EducationLibrary: reading areas500190.6806.3 Table 6.3
EducationKindergarten play room300190.6806.3 Table 6.3
EducationKindergarten nursery / craft room300190.6806.3 Table 6.3
HealthcareWaiting rooms200220.4806.4 Table 6.4
HealthcareCorridors: daytime200220.4806.4 Table 6.4
HealthcareCorridors: night50220.4806.4 Table 6.4Night circuit with low glare and warm CCT
HealthcareWard: general lighting100190.4806.4 Table 6.4
HealthcareWard: reading light300190.6806.4 Table 6.4
HealthcareWard: simple examination300190.6806.4 Table 6.4
HealthcareExamination and treatment1000190.7906.4 Table 6.4Ra 90+ for tissue colour assessment
HealthcareNight watch / observation5——806.4 Table 6.4
HealthcareConsulting room500190.6906.4 Table 6.4
HealthcareDental treatment area (general)1000190.7906.4 Table 6.4Task light excluded from the general value
HealthcarePharmacy dispensing and prescription area500190.6906.4 Table 6.4
HealthcareSenior care living room300190.6906.4 Table 6.4Consider 500 lx and higher uniformity for residents 65+
RetailSales area300220.4806.6 Table 6.6Accent lighting is additional to the maintained task value
RetailTill area500190.6806.6 Table 6.6
RetailWrapper table500190.6806.6 Table 6.6
RetailSupermarket general sales floor500220.6806.6 Table 6.6Fresh food zones typically Ra 90+ with dedicated CCT
RetailFashion fitting rooms300190.6906.6 Table 6.6Vertical and cylindrical illuminance dominate
RetailJewellery display case500190.6906.6 Table 6.6Sparkle needs narrow beam accent, not higher ambient
RetailShopping mall common circulation200220.4806.6 Table 6.6
HospitalityHotel reception / cashier / porters desk300220.6806.5 Table 6.5
HospitalityHotel kitchen500220.6806.5 Table 6.5
HospitalityRestaurant buffet300220.6806.5 Table 6.5Dining room itself is a design task, not a fixed value
HospitalitySelf-service restaurant200220.4806.5 Table 6.5
HospitalityConference and multipurpose rooms500190.6806.5 Table 6.5
HospitalityHotel corridors and stairs100250.4806.5 Table 6.5
IndustryAssembly: rough work200250.4806.10 Table 6.10
IndustryAssembly: medium work300250.6806.10 Table 6.10
IndustryAssembly: fine work500220.6806.10 Table 6.10
IndustryAssembly: precision work750190.7806.10 Table 6.10
IndustryInspection and testing500190.6806.10 Table 6.10
IndustryColour inspection / colour matching1000160.7906.10 Table 6.10D65 or 5000 K, Ra 90+, TM-30 Rf/Rg reported
IndustrySMT / electronics cleanroom bench750190.7806.10 Table 6.10IP54 and sealed housings typical
IndustryPharmaceutical GMP production500220.6806.10 Table 6.10Flush, cleanable, IP65 recessed luminaires
IndustryPacking and dispatch300250.6806.10 Table 6.10
StorageStore rooms and stock rooms100250.4606.10 Table 6.10
StorageAisles with traffic (unoccupied racking)150220.4606.10 Table 6.10Vertical illuminance on rack face governs picking
StorageCold storage150250.4606.10 Table 6.10Rated for -30 C ambient, instant restrike
TransportAirport / rail concourse and ticket hall200220.4806.8 Table 6.8
TransportCheck-in and ticket desks300220.6806.8 Table 6.8
TransportMetro concourse200220.4806.8 Table 6.8
TransportCovered platforms100—0.4606.8 Table 6.8
TransportEscalators and travelators150250.4806.8 Table 6.8
TransportIndoor car park: traffic lanes75250.4606.8 Table 6.8
TransportIndoor car park: parking areas75—0.4606.8 Table 6.8
TransportIndoor car park: entrance ramp, daytime300250.4606.8 Table 6.8Transition zone to avoid adaptation glare
SportSports hall: training and recreation300220.6806.7 Table 6.7
SportSports hall: competition500220.7806.7 Table 6.7Broadcast levels are set by the sport federation, not EN 12464-1
SportIndoor swimming pool300220.6806.7 Table 6.7IP65, corrosion resistant, low veiling reflection on water
SportFitness and yoga studio300220.6806.7 Table 6.7
TechnicalControl rooms500190.6806.9 Table 6.9
TechnicalPlant rooms, switch rooms, cable rooms200250.4606.9 Table 6.9
TechnicalData centre white space aisles300220.6806.9 Table 6.9Vertical illuminance on rack face is the real task
PublicEntrance halls and lobbies100220.4806.1 Table 6.1
PublicCirculation areas and corridors100280.4406.1 Table 6.1
PublicStairs, escalators100250.4406.1 Table 6.1
PublicCanteens and pantries200220.4806.1 Table 6.1
PublicRest and first aid rooms200220.4806.1 Table 6.1
PublicSanitary rooms and washrooms200250.4806.1 Table 6.1
PublicCourthouse courtroom300220.6806.1 Table 6.1500 lx on the bench and evidence table
PublicMuseum and gallery: light-sensitive exhibits50190.6906.6 / CIE 157Annual exposure limit governs; 50 lx and UV/IR free

How to use these values in a tender