EN 12464-1 lux level table: Em, UGR, Uo and Ra by room
The values below follow EN 12464-1:2021 for 90 common indoor task areas — maintained illuminance Em, glare limit UGR, uniformity Uo and colour rendering Ra. Use it for a first sizing pass and a specification cross-check, then confirm against your national adoption (DIN EN, NF EN, NEN-EN, UNI EN, UNE-EN, BS EN) and the project brief. This table is a design aid, not a replacement for the standard.
Free to reuse in tender documents and design reports with a credit link to led-project-light.com.
90 of 90 rows
| Building type | Task or activity area | Em (lx) | UGR max | Uo min | Ra min | Reference | Design notes |
|---|---|---|---|---|---|---|---|
| Office | Filing, copying, circulation inside the office | 300 | 19 | 0.4 | 80 | 6.2 Table 6.2 | |
| Office | Writing, typing, reading, data processing | 500 | 19 | 0.6 | 80 | 6.2 Table 6.2 | Add 750 lx for open-plan desks used by older occupants |
| Office | Technical drawing by hand | 750 | 16 | 0.7 | 80 | 6.2 Table 6.2 | |
| Office | CAD workstations | 500 | 19 | 0.6 | 80 | 6.2 Table 6.2 | Limit screen-reflected luminance to 200-1500 cd/m2 |
| Office | Conference and meeting rooms | 500 | 19 | 0.6 | 80 | 6.2 Table 6.2 | Dimmable to 200 lx for projection |
| Office | Reception desk | 300 | 22 | 0.6 | 80 | 6.2 Table 6.2 | |
| Office | Archives | 200 | 25 | 0.4 | 80 | 6.2 Table 6.2 | |
| Office | Coworking / flexible desking | 500 | 19 | 0.6 | 80 | 6.2 Table 6.2 | Zone controls per desk cluster |
| Education | Classroom, general teaching | 300 | 19 | 0.6 | 80 | 6.3 Table 6.3 | |
| Education | Classroom for evening classes and adult education | 500 | 19 | 0.6 | 80 | 6.3 Table 6.3 | |
| Education | Lecture hall | 500 | 19 | 0.6 | 80 | 6.3 Table 6.3 | Dimmable, separate front-of-room circuit |
| Education | Blackboard / whiteboard | 500 | 19 | 0.7 | 80 | 6.3 Table 6.3 | Asymmetric wallwasher, avoid specular reflection |
| Education | Demonstration table | 500 | 19 | 0.7 | 80 | 6.3 Table 6.3 | |
| Education | Art rooms | 500 | 19 | 0.6 | 80 | 6.3 Table 6.3 | |
| Education | Art rooms in art schools | 750 | 19 | 0.7 | 90 | 6.3 Table 6.3 | Ra 90+ and 5000 K for colour judgement |
| Education | Technical drawing rooms | 750 | 16 | 0.7 | 80 | 6.3 Table 6.3 | |
| Education | Practical rooms and laboratories | 500 | 19 | 0.6 | 80 | 6.3 Table 6.3 | |
| Education | Handicraft and teaching workshops | 500 | 19 | 0.6 | 80 | 6.3 Table 6.3 | |
| Education | Music practice rooms | 300 | 19 | 0.6 | 80 | 6.3 Table 6.3 | |
| Education | Computer practice rooms | 300 | 19 | 0.6 | 80 | 6.3 Table 6.3 | |
| Education | Preparation rooms and workshops | 500 | 22 | 0.6 | 80 | 6.3 Table 6.3 | |
| Education | Entrance halls | 200 | 22 | 0.4 | 80 | 6.3 Table 6.3 | |
| Education | Circulation areas and corridors | 100 | 25 | 0.4 | 80 | 6.3 Table 6.3 | |
| Education | Stairs | 150 | 25 | 0.4 | 80 | 6.3 Table 6.3 | Vertical illuminance on treads is the design driver |
| Education | Student common rooms and assembly halls | 200 | 22 | 0.4 | 80 | 6.3 Table 6.3 | |
| Education | Teachers rooms | 300 | 19 | 0.6 | 80 | 6.3 Table 6.3 | |
| Education | Library: bookshelves | 200 | 19 | 0.6 | 80 | 6.3 Table 6.3 | Vertical illuminance on shelf face |
| Education | Library: reading areas | 500 | 19 | 0.6 | 80 | 6.3 Table 6.3 | |
| Education | Kindergarten play room | 300 | 19 | 0.6 | 80 | 6.3 Table 6.3 | |
| Education | Kindergarten nursery / craft room | 300 | 19 | 0.6 | 80 | 6.3 Table 6.3 | |
| Healthcare | Waiting rooms | 200 | 22 | 0.4 | 80 | 6.4 Table 6.4 | |
| Healthcare | Corridors: daytime | 200 | 22 | 0.4 | 80 | 6.4 Table 6.4 | |
| Healthcare | Corridors: night | 50 | 22 | 0.4 | 80 | 6.4 Table 6.4 | Night circuit with low glare and warm CCT |
| Healthcare | Ward: general lighting | 100 | 19 | 0.4 | 80 | 6.4 Table 6.4 | |
| Healthcare | Ward: reading light | 300 | 19 | 0.6 | 80 | 6.4 Table 6.4 | |
| Healthcare | Ward: simple examination | 300 | 19 | 0.6 | 80 | 6.4 Table 6.4 | |
| Healthcare | Examination and treatment | 1000 | 19 | 0.7 | 90 | 6.4 Table 6.4 | Ra 90+ for tissue colour assessment |
| Healthcare | Night watch / observation | 5 | — | — | 80 | 6.4 Table 6.4 | |
| Healthcare | Consulting room | 500 | 19 | 0.6 | 90 | 6.4 Table 6.4 | |
| Healthcare | Dental treatment area (general) | 1000 | 19 | 0.7 | 90 | 6.4 Table 6.4 | Task light excluded from the general value |
| Healthcare | Pharmacy dispensing and prescription area | 500 | 19 | 0.6 | 90 | 6.4 Table 6.4 | |
| Healthcare | Senior care living room | 300 | 19 | 0.6 | 90 | 6.4 Table 6.4 | Consider 500 lx and higher uniformity for residents 65+ |
| Retail | Sales area | 300 | 22 | 0.4 | 80 | 6.6 Table 6.6 | Accent lighting is additional to the maintained task value |
| Retail | Till area | 500 | 19 | 0.6 | 80 | 6.6 Table 6.6 | |
| Retail | Wrapper table | 500 | 19 | 0.6 | 80 | 6.6 Table 6.6 | |
| Retail | Supermarket general sales floor | 500 | 22 | 0.6 | 80 | 6.6 Table 6.6 | Fresh food zones typically Ra 90+ with dedicated CCT |
| Retail | Fashion fitting rooms | 300 | 19 | 0.6 | 90 | 6.6 Table 6.6 | Vertical and cylindrical illuminance dominate |
| Retail | Jewellery display case | 500 | 19 | 0.6 | 90 | 6.6 Table 6.6 | Sparkle needs narrow beam accent, not higher ambient |
| Retail | Shopping mall common circulation | 200 | 22 | 0.4 | 80 | 6.6 Table 6.6 | |
| Hospitality | Hotel reception / cashier / porters desk | 300 | 22 | 0.6 | 80 | 6.5 Table 6.5 | |
| Hospitality | Hotel kitchen | 500 | 22 | 0.6 | 80 | 6.5 Table 6.5 | |
| Hospitality | Restaurant buffet | 300 | 22 | 0.6 | 80 | 6.5 Table 6.5 | Dining room itself is a design task, not a fixed value |
| Hospitality | Self-service restaurant | 200 | 22 | 0.4 | 80 | 6.5 Table 6.5 | |
| Hospitality | Conference and multipurpose rooms | 500 | 19 | 0.6 | 80 | 6.5 Table 6.5 | |
| Hospitality | Hotel corridors and stairs | 100 | 25 | 0.4 | 80 | 6.5 Table 6.5 | |
| Industry | Assembly: rough work | 200 | 25 | 0.4 | 80 | 6.10 Table 6.10 | |
| Industry | Assembly: medium work | 300 | 25 | 0.6 | 80 | 6.10 Table 6.10 | |
| Industry | Assembly: fine work | 500 | 22 | 0.6 | 80 | 6.10 Table 6.10 | |
| Industry | Assembly: precision work | 750 | 19 | 0.7 | 80 | 6.10 Table 6.10 | |
| Industry | Inspection and testing | 500 | 19 | 0.6 | 80 | 6.10 Table 6.10 | |
| Industry | Colour inspection / colour matching | 1000 | 16 | 0.7 | 90 | 6.10 Table 6.10 | D65 or 5000 K, Ra 90+, TM-30 Rf/Rg reported |
| Industry | SMT / electronics cleanroom bench | 750 | 19 | 0.7 | 80 | 6.10 Table 6.10 | IP54 and sealed housings typical |
| Industry | Pharmaceutical GMP production | 500 | 22 | 0.6 | 80 | 6.10 Table 6.10 | Flush, cleanable, IP65 recessed luminaires |
| Industry | Packing and dispatch | 300 | 25 | 0.6 | 80 | 6.10 Table 6.10 | |
| Storage | Store rooms and stock rooms | 100 | 25 | 0.4 | 60 | 6.10 Table 6.10 | |
| Storage | Aisles with traffic (unoccupied racking) | 150 | 22 | 0.4 | 60 | 6.10 Table 6.10 | Vertical illuminance on rack face governs picking |
| Storage | Cold storage | 150 | 25 | 0.4 | 60 | 6.10 Table 6.10 | Rated for -30 C ambient, instant restrike |
| Transport | Airport / rail concourse and ticket hall | 200 | 22 | 0.4 | 80 | 6.8 Table 6.8 | |
| Transport | Check-in and ticket desks | 300 | 22 | 0.6 | 80 | 6.8 Table 6.8 | |
| Transport | Metro concourse | 200 | 22 | 0.4 | 80 | 6.8 Table 6.8 | |
| Transport | Covered platforms | 100 | — | 0.4 | 60 | 6.8 Table 6.8 | |
| Transport | Escalators and travelators | 150 | 25 | 0.4 | 80 | 6.8 Table 6.8 | |
| Transport | Indoor car park: traffic lanes | 75 | 25 | 0.4 | 60 | 6.8 Table 6.8 | |
| Transport | Indoor car park: parking areas | 75 | — | 0.4 | 60 | 6.8 Table 6.8 | |
| Transport | Indoor car park: entrance ramp, daytime | 300 | 25 | 0.4 | 60 | 6.8 Table 6.8 | Transition zone to avoid adaptation glare |
| Sport | Sports hall: training and recreation | 300 | 22 | 0.6 | 80 | 6.7 Table 6.7 | |
| Sport | Sports hall: competition | 500 | 22 | 0.7 | 80 | 6.7 Table 6.7 | Broadcast levels are set by the sport federation, not EN 12464-1 |
| Sport | Indoor swimming pool | 300 | 22 | 0.6 | 80 | 6.7 Table 6.7 | IP65, corrosion resistant, low veiling reflection on water |
| Sport | Fitness and yoga studio | 300 | 22 | 0.6 | 80 | 6.7 Table 6.7 | |
| Technical | Control rooms | 500 | 19 | 0.6 | 80 | 6.9 Table 6.9 | |
| Technical | Plant rooms, switch rooms, cable rooms | 200 | 25 | 0.4 | 60 | 6.9 Table 6.9 | |
| Technical | Data centre white space aisles | 300 | 22 | 0.6 | 80 | 6.9 Table 6.9 | Vertical illuminance on rack face is the real task |
| Public | Entrance halls and lobbies | 100 | 22 | 0.4 | 80 | 6.1 Table 6.1 | |
| Public | Circulation areas and corridors | 100 | 28 | 0.4 | 40 | 6.1 Table 6.1 | |
| Public | Stairs, escalators | 100 | 25 | 0.4 | 40 | 6.1 Table 6.1 | |
| Public | Canteens and pantries | 200 | 22 | 0.4 | 80 | 6.1 Table 6.1 | |
| Public | Rest and first aid rooms | 200 | 22 | 0.4 | 80 | 6.1 Table 6.1 | |
| Public | Sanitary rooms and washrooms | 200 | 25 | 0.4 | 80 | 6.1 Table 6.1 | |
| Public | Courthouse courtroom | 300 | 22 | 0.6 | 80 | 6.1 Table 6.1 | 500 lx on the bench and evidence table |
| Public | Museum and gallery: light-sensitive exhibits | 50 | 19 | 0.6 | 90 | 6.6 / CIE 157 | Annual exposure limit governs; 50 lx and UV/IR free |
How to use these values in a tender
- Specify Em maintained on the task area, not initial lux, and state the maintenance factor used.
- Pair every Em value with UGR, Uo and Ra — an Em-only specification is what lets non-compliant fixtures in.
- Ask for a DIALux evo report plus the photometric file (IES or LDT) that produced it.
- Add the control protocol (DALI-2 / D4i, Casambi) and the flicker limit (PstLM < 1.0 at every dim level).